15. Maintenance
15 Maintenance
15.1 General
The boiler requires little maintenance if it is correctly set. The boiler only requires an annual check and cleaning if necessary.
15.2 Inspection
The annual inspection of the boiler can be restricted to the following
operations:
- Measure the combustion and check the operation
- Clean the siphon
- Checking condensates discharge
- Checking the ignition electrode and the ionization sensor
- Set the gap between the ignition electrodes
:
3 to 4 mm
- Check the concentric flue gas evacuation and combustive air inlet
pipes
- Checking the hydraulic pressure (minimum 0.8 bar). Add water to the
installation if necessary (Recommended pressure
:
1.5 bar)
- Check the ionization current
:
4 to 9 µA.
15.2.1 Checking the combustion in the boiler
This check can be carried out by measuring the CO
2
/O
2
content in
the combusted gas evacuation pipe at the measurement point
.
All countries except Belgium:
Bring the boiler to maximum output up to a water temperature of
around 70°C
.
Correct the burner setting to ±0.3% CO
2
; ±0.2% O
2
.
For Belgium:
* Approximate CO
2
content: 7.5% Approximate O
2
content: 7.3%
The temperature of the combusted gases can also be measured at the measurement point in the evacuation pipe. The temperature of the
combusted gas must not exceed the temperature of the return water by more than 30 °C. If it turns out that boiler combustion has not been
optimised after this check, clean the installation.
Boilers
Fan speed Natural gas G20/G25 Propane
rpm
O
2
CO
2
O
2
CO
2
Maximum output
Minimum
output
Start-up output
% % % %
Natural gas
Propane
Natural gas
Propane
DTGE130-
35,
DTG130-35
about 4600 about 4200 about 1100
2500 2500 4.8/4.8 ± 0.2 9.0/9.0 ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-45
about 5200 about 4600 about 1100
2500 2500 4.8/4.8 ± 0.2 9.0/9.0 ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-65
about 5200 about 4600 about 1200
2500 2500 4.8/4.8 ± 0.2 9.0/9.0 ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-90
about 6200 about 6100 about 1200
2500 2000 3.9/3.9 ± 0.2 9.5/9.5 ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-115
about 7000 about 6700 about 1300
2500 2000 4.8/3.9 ± 0.2 9.0/9.5 ± 0.3 5.7 ± 1.0 10.0 ± 0.7
Boilers
Fan speed Natural gas G20/G25 Propane
rpm
O
2
CO
2
O
2
CO
2
Maximum output
Minimum
output
Start-up output
% % % %
Natural gas
Propane
Natural gas
Propane
DTGE130-
35,
DTG130-35
about 4600 about 4200 about 1100*
2500 2500 4.8/* ± 0.2 9.0/* ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-45
about 5200 about 4600 about 1100
2500 2500 4.8/* ± 0.2 9.0/* ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-65
about 5200 about 4600 about 1200
2500 2500 4.8/* ± 0.2 9.0/* ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-90
about 6200 about 6100 about 1200
2500 2000 3.9/3.9 ± 0.2 9.5/9.5 ± 0.3 4.8 ± 0.2 10.7 ± 0.3
DTG130-115
about 7000 about 6700 about 1300
2500 2000 4.8/3.9 ± 0.2 9.0/9.5 ± 0.3 5.7 ± 1.0 10.0 ± 0.7