15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
12. Installer settings
12.1 "Professional" settings
* The line or title is only displayed for the options, circuits or
sensors actually connected.
(1) Français - Deutsch - English - Polski - Italiano - Español -
Nederlands - Русский
At the end of the intervention, the data is stored after 2 minutes
or by closing the flap.
Press Display Parameter set Factory setting
Adjustment
range
K
5
seconds then
I
#LANGUAGE Language selection using keys
or
FRANCAIS
FRANCAIS (1)
J
then
I
#LIMITED TEMP. Setting the temperature limits using keys
or
BOILER MAX Maximum boiler temperature and boiler setting if
producing domestic hot water
.
80 °C 30 to 90 °C -
BOILER MIN
Minimum boiler temperature
.
15 °C 10 to 50 °C -
HCZP D Bottom of curve temperature in comfort mode (Circuit
A).
OFF
OFF or 20 to
90 °C
-
HCZP N Bottom of curve temperature in reduced mode (Circuit
A).
OFF
OFF or 20 to
90 °C
-
HCZP D B* Boiler instruction setting when the circuit is a pool on
request
.
OFF
OFF or 20 to
90 °C
-
MAX. CIRC. A* Maximum outlet temperature (Circuit A). 75 °C 20 to 90 °C -
FL.DRY. A*
Drying the floor (Circuit A)
.
OFF
OFF or 20 to
90 °C
MAX. CIRC. B * Maximum outlet temperature (Circuit B). 50 °C 20 to 90 °C -
FL.DRY. B *
Drying the floor (Circuit B)
.
OFF
OFF or 20 to
55 °C
-
MIN. CIRC. B * Minimum outlet temperature activated by the
installation's antifreeze function (Circuit B).
20 °C 10 to 30 °C -
MAX. CIRC. C * Maximum outlet temperature (Circuit C). 50 °C 20 to 90 °C -
FL.DRY. C *
Drying the floor (Circuit C).
OFF
OFF or 20 to
55 °C
-
MIN. CIRC. C * Minimum outlet temperature activated by the
installation's antifreeze function (Circuit C).
20 °C 10 to 50 °C -
OUT.ANTIFREEZE Outside temperature activating the installation's
antifreeze function
.
+ 3°C -8 to +1C -
MAX.R.HEAT(%) Maximum boiler output during heating 100 % 20-100 %
MAX.DHW(%) Maximum boiler output in DHW 100 % 20-100 %