38
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
9. Commissioning
9.3.1 DTGE130-35 / DTG130-35 / DTG130-45 / DTG130-65 / DTG130-90
For Belgium: Any work on the gas block must be carried
out by a factory technician (For example: SERV’élite).
The boiler is preset in the factory to operate on natural gas
G20, IWs = 15.0 kWh/m
3
. Connection pressure (mbar) 20.
Maximum power of the burner (Factory setting in kW)
The burner is set exclusively by checking the CO
2
and O
2
level in the
flue gases at maximum and minimum output.
Compare the information on the appliance's rating plate with the type
of gas available in situ.
If this is natural gas, the boiler can be commissioned without making
other settings (Ws = 12.0-15.7 kWh/m3).
` Switch on the electrical supply.
` Starting the burner up.
The appliance must be powered by a circuit containing an omnipolar
switch with an opening distance 3 mm.
The earth connection shall comply with standard NF C 15 100.
Take the boiler up to maximum power.
` Open the panel flap.
` Press key
%O
and
$P
simultaneously for 2 seconds.
` Set the burner output using the + and - keys.
= Maximum
power of the burner.
` Remove the top panel.
` Remove the plastic plug from the measurement tube.
` Check the CO
2
and O
2
level in the flue gases using the
measuring device.
C001258-B
6
7
8
Boilers
DTG E
130-35
DTG130-
35
DTG130-
45
DTG130-
65
DTG130-
90
Heating mode
(100 %) (Hi / Hs)
33.5 /
37.2
33.5 /
37.2
41.2 /
45.7
62.0 /
68.8
86.0 /
95.5
Domestic hot
water mode
(100%) (Hi / Hs)
33.5 /
37.2
33.5 /
37.2
41.2 /
45.7
62.0 /
68.8
86.0 /
95.5
Comentários a estes Manuais