64
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
12. Installer settings
* The line or title is only displayed for the options, circuits or
sensors actually connected.
** The lines are only displayed one minute after the boiler has
been switched on. The lines are never displayed when the safety
control box is locked or during an MCBA COM. FAULT failure.
Press Display Output or input parameter status
J
then
I
#TEST INPUTS
PHONE REM. Bridge on telephone input (1 = presence, 2 = absence)
FLAME Flame (1 = presence, 2 = absence)
FAILURE Fault display: yes (1) or no (0)
SEQ. Operating mode: STANDBY - FAN - IGNITION - ON - PENDING - OFF
TYPE Boiler type + Control value for the technician
VER. PROTOCOL Control value for the technician
R.CTRL A: ON/FF* Remote control A (yes = presence, no = absence)
R.CTRL B: ON/OFF* Remote control B (yes = presence, no = absence)
R.CTRL B: ON/OFF* Remote control C (yes = presence, no = absence)
J
then
I
#CONFIGURATION
MODE:: MONO/ALL.CIRC. To chose if the exemption made for one remote control applies to a single circuit (MONO) or if it
must be transmitted to a group of circuits (ALL CIRC)
CASCADE NO, 1 TO 10 OFF: The boiler is not in a cascade
1: Boiler self-standing or Master boiler
2 to 10: Secondary boiler
FUNCT: CASC:/PARA* Operation in cascade
(See installation instructions "Cascade Management")
*PARALLEL CASC.
10°
(minimum
: -10°, maximum: 20°)
Outside temperature at which all boilers are started up
(See installation instructions "Cascade Management")
TYPE** Type of box: 35 kW, 45 kW, 65 kW, 90 kW, 115 kW
ST.VENT.** Fan start up speed (rpm)
Factory setting (natural gas): 35 kW: 2500, 45 kW: 2500, 65 kW: 2500, 90 kW: 2500,
115 kW: 2500
Setting range: 2000 to 3000 (rpm)
MIN.VENT.** Minimum fan speed (rpm)
Factory setting (natural gas): 35 kW: 1100, 45 kW: 1100, 65 kW: 1200, 90 kW: 1200,
115 kW: 1300
Setting range: 1000 to 6000 (rpm)
MAX.VENT.** Maximum fan speed (rpm)
Factory setting (natural gas): 35 kW: 4600, 45 kW: 5200, 65 kW: 5200, 90 kW: 6200,
115 kW: 7000
Setting range: 1000 to 7000 (rpm)
J
then
I
#REVISION Activates the function generating a REVISION display when the date programmed is reached
REVISION HOUR* Time at which the REVISION display appears
REV. YEAR: OFF/AAAA Year in which the REVISION display appears
REVIS. MONTH* Month in which the REVISION display appears
REVISION DATE* Day on which the REVISION display appears