13. Adapting to another gas type
DTG130-115
Changing from Natural Gas to Propane requires:
- Installing the conversion kit.
- the setting of the burner,
- the setting of the maximum fan speed.
` Open the top flap.
` Switch the On/Off switch on Off.
` Access the heating body and the gas valve unit
Z
See chapter Cleaning and maintenance.
` Put the gas block in place.
Z
See Assembly instructions, Propane conversion kit.
` Place the stop/start switch on On.
` Set the maximum fan speed to a value of:
- 6700 rpm
:
DTG130-115.
Z
See chapter Parameter and input/output check (mode
tests) "Table: MAX.VENT." (page 63)
` Take the boiler up to maximum power.
- Tilt the flap on the control panel
.
- Press key
%O
and
$P
simultaneously for 2 seconds
.
- Set the burner output using the
+
and
-
keys
.
: Maximum power of the burner
` Remove the plastic plug from the measurement tube.
` Measure the CO
2
or O
2
level in the flue gases.
Z
See Table page 39.
` Set: CO
2
to 10.7 ±0.3% or O
2
to 4.8 ±0.2%.
` Check the flame via the flame inspection window. It must not go
out. The flame must be stable and blue in colour with orange
particles around the edge of the burner.
` Set the burner output to minimum using the - key.
: Minimum
output.
` Measure the CO
2
or O
2
level in the flue gases.