DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
9. Commissioning
9 Commissioning
Initial commissioning must be done by a qualified
professional.
Before start-up, the heating installation must be completely emptied
and rinsed.
Operation while the condensation water siphon is empty may
damage the boiler.
9.1 Filling the system
` Fill the installation with water.
` Vent the heating installation.
` Fill the siphon with water.
` Check the pressure of the installation (Minimum pressure 0.8
bar; Recommended pressure 1.5 bar; Maximum pressure 4
bar).
` Carry out a water tightness check.
` Top up with more water if necessary.
9.2 Check points before commissioning
For Belgium: Any work on the gas valve unit is authorised
only if carried out by a qualified professional.
9.2.1 Checking the gas supply pressure
1. Close the gas valve.
2. Loosen the screw on the measurement connection by 2 turn
(Marker
).
3. Connect the manometer.
4. Open the gas valve.
5. Check the pressure of the gas connection on the measurement
connection. The boiler is preset in the factory to operate on
natural gas.
If the pressure exceeds the authorised pressure range,
suspend commissioning (Authorised pressure range, see
page: 9). Inform the gas supply company.
The pressure measured on
is the supply pressure
reduced by the pressure drop of internal gas pipe.
6. Close the gas valve. Disconnect the manometer.
7. Tighten screw
.
8. Open the gas valve. Check the seal.
C001248
1
DTG... 130...
DTG (E) 35 DTG 45 DTG 65 DTG 90 DTG 115
P min
(1)
P nom
(2)
P max
(3)
P min
(1)
P nom
(2)
P max
(3)
P min
(1)
P nom
(2)
P max
(3)
P min
(1)
P nom
(2)
P max
(3)
P min
(1)
P nom
(2)
P max
(3)
Natural gas H (20 mbar)
Supply pressure 17 20 25 17 20 25 17 20 25 17 20 25 17 20 25
Pressure
16.2 19.2 24.2 15.8 18.8 23.8 14.5 17.5 22.5 13.3 16.3 21.3 13.1 16.1 21.1
Natural gas L (25 mbar)
Supply pressure 20 25 30 20 25 30 20 25 30 20 25 30 20 25 30
Pressure
18.8 23.8 28.8 18.2 23.2 28.2 16.3 21.3 27.3 14.5 19.5 24.5 14.2 19.2 24.2
Propane (37 mbar)
Supply pressure 25 37 45 25 37 45 25 37 45 25 37 45 25 37 45
Pressure
24.7 36.7 44.7 24.5 36.5 44.5 24 36 44 23.5 35.5 43.5 23.4 35.4 43.4