15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
10. Messages - Alarms
• BOILER S.FAIL., BACK S.FAILURE
The boiler will no longer satisfy any heating requests.
• OUTSI. S.FAIL.
- The boiler operates on
BOILER MAX
temperature
.
- The valve setting is no longer ensured but monitoring the
maximum temperature of the circuit after the valve is ensured.
- Valves may be manually operated.
- Reheating the domestic hot water remains ensured
.
• DHW S. FAILURE
- Heating of domestic hot water is no longer ensured
.
- The load pump operates.
- The load temperature of the dhw tank is the same as the boiler.
• OUTL S.B FAIL., OUTL S.C FAIL.
- The pump operates
.
- The valve is no longer powered and can be adjusted manually.
• ROOM S.A FAIL., ROOM S.B FAIL., ROOM S.C FAIL.
The circuit concerned operates without any influence from the
room sensor.
• SMOKE S. FAIL.
Flue gas sensor defective. The boiler goes into safety shutdown.
• SWIM.P. S.FAIL
Pool reheating is independent of its temperature.
• ST.TANK S.FAIL
The hot water storage tank reheating operation is no longer
assured.
The 10 latest faults appearing on the display are memorised in
the paragraph #HISTORY D..
Z
See chapter Parameter and input/output check (mode tests).
Faults Probable causes Action
FAN OFF FAIL The fan is not working
Fan defective
. Check the fan wiring (corrosion of the connection). Safety control box
defective
.
FAN ON FAIL The fan is working constantly
Electrical connections broken
. Fan control is defective (replace the fan).
BOILER S.FAIL. Boiler sensor defective
Check the link and the connectors
. Replace the sensor if necessary. Reset the boiler.
PARASIT FLAME Detection of a parasite flame
Check the seals on all gas connections
. Set the gap between the ignition electrodes.
Check that the surface of the burner does not have any fibre residues
.
STB BOILER Outlet temperature > 110°C
Check the STB safety thermostat and the wiring
. Bleed the boiler. Check the boiler
pump
. Check the hydraulic circuit on the installation.
STB SMOKE Flue gas temperature > 100°C
Check flue gas discharge
. Replace it if necessary.
STB BACK Return temperature too high
Check the wiring
. Bleed the boiler. Check the boiler pump. Check the hydraulic circuit on
the installation
.