15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
10. Messages - Alarms
BOILER S.FAIL., BACK S.FAILURE
The boiler will no longer satisfy any heating requests.
OUTSI. S.FAIL.
- The boiler operates on
BOILER MAX
temperature
.
- The valve setting is no longer ensured but monitoring the
maximum temperature of the circuit after the valve is ensured.
- Valves may be manually operated.
- Reheating the domestic hot water remains ensured
.
DHW S. FAILURE
- Heating of domestic hot water is no longer ensured
.
- The load pump operates.
- The load temperature of the dhw tank is the same as the boiler.
OUTL S.B FAIL., OUTL S.C FAIL.
- The pump operates
.
- The valve is no longer powered and can be adjusted manually.
ROOM S.A FAIL., ROOM S.B FAIL., ROOM S.C FAIL.
The circuit concerned operates without any influence from the
room sensor.
SMOKE S. FAIL.
Flue gas sensor defective. The boiler goes into safety shutdown.
SWIM.P. S.FAIL
Pool reheating is independent of its temperature.
ST.TANK S.FAIL
The hot water storage tank reheating operation is no longer
assured.
The 10 latest faults appearing on the display are memorised in
the paragraph #HISTORY D..
Z
See chapter Parameter and input/output check (mode tests).
Faults Probable causes Action
FAN OFF FAIL The fan is not working
Fan defective
. Check the fan wiring (corrosion of the connection). Safety control box
defective
.
FAN ON FAIL The fan is working constantly
Electrical connections broken
. Fan control is defective (replace the fan).
BOILER S.FAIL. Boiler sensor defective
Check the link and the connectors
. Replace the sensor if necessary. Reset the boiler.
PARASIT FLAME Detection of a parasite flame
Check the seals on all gas connections
. Set the gap between the ignition electrodes.
Check that the surface of the burner does not have any fibre residues
.
STB BOILER Outlet temperature > 110°C
Check the STB safety thermostat and the wiring
. Bleed the boiler. Check the boiler
pump
. Check the hydraulic circuit on the installation.
STB SMOKE Flue gas temperature > 100°C
Check flue gas discharge
. Replace it if necessary.
STB BACK Return temperature too high
Check the wiring
. Bleed the boiler. Check the boiler pump. Check the hydraulic circuit on
the installation
.