58
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
12. Installer settings
` BUILD. INERTIA
Modification of the factory setting is only useful in exceptional
cases.
0 for a building with low thermal inertia.
3 for a building with normal thermal inertia.
10 for a building with high thermal inertia.
` PUMP A:
- In the PUMP A parameter, outlet
9
controls circuit A and can be
used as a load pump for DHW production with a reversal valve on
the DHW outlet.
Note: For DTGE-35 boilers, set the parameter PUMP A to
BOILER (see Installation instructions).
- In the HOT parameter, pump A is started up whenever there is a
secondary request (circuits A, B, C, DHW or VM).
` CIRC. CURVE ...
Independent setting for each circuit.
- Heating curve circuit A
The factory setting of the heating curve is 1.5.
- Heating curve circuit B or C
The factory setting of the heating curve is 0.7.
` ROOM S.INFL
Used to adjust the influence of the room sensor on the water
temperature for the circuit concerned.
Maximum boiler temperature: 90 °C
(factory setting 80 °C)
x
Outside temperature (°C)
y Water flow temperature (°C)
Maximum boiler temperature (factory setting 50 °C)
Minimum boiler temperature (factory setting 20 °C)
x
Outside temperature (°C)
y
Water flow temperature (°C)
0 No influence (remote control fitted in a location with no influence)
1 Slight influence
3 Average influence (recommended)
10 Room thermostat type operation