66
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
13. Adapting to another gas type
` Switch the On/Off switch on Off.
` Preset the burner by turning the "max output" setting screw
:
- by 3 turns to the right
:
DTGE130-35, DTG130-35, DTG130-45
.
- by 4 turns to the right
:
DTG130-65
.
` Install the conversion kit on DTG130-90.
` Place the stop/start switch on On.
` Set the maximum fan speed to a value of:
- 4200 rpm
:
DTGE130-35, DTG130-35
.
- 4600 rpm
:
DTG130-45, DTG130-65
.
- 6100 rpm
:
DTG130-90
.
Z
See chapter: Parameter and input/output check (mode
tests) ; "Table: MAX.VENT." (page 63).
` Set the fan start-up speed to a value of 2000 rpm: DTG130-90.
Z
See chapter: Parameter and input/output check (mode
tests) ; "Table: ST.VENT." (page 63).
` Take the boiler up to maximum power.
- Tilt the flap on the control panel
.
- Press key
%O
and
$P
simultaneously for 2 seconds
.
- Set the burner output using the
+
and
-
keys
.
: Maximum power of the burner
` Remove the plastic plug from the measurement tube.
` Measure the CO
2
or O
2
level in the flue gases.
` Set: CO
2
to 10.7 ±0.3% or O
2
to 4.8 ±0.2%.
` Check the flame via the flame inspection window. It must not go
out. The flame must be stable and blue in colour with orange
particles around the edge of the burner.
` Set the burner output to minimum using the - key.
: Minimum
output.
` Measure the CO
2
or O
2
level in the flue gases.
` Modify the "min output" setting with the setting screw
.
` Check the output delivered again.
` Adjust if necessary.
For Switzerland
: The maximum limit values authorised by the
OPAIR federal order on air protection regarding CO and NOx must
be checked using measurements made in the place of installation.
` When the setting is correct, close the flap.
` Switch the On/Off switch on Off.
` Remove the measuring equipment.
` Replace the plastic plug onto the measuring tube.
C000925-B